Home Forums GetTesting TechEx PAT on hob extractor fan (with plug)

Viewing 3 posts - 1 through 3 (of 3 total)
  • Author
    Posts
  • #7274
    Jenny
    Participant

    No matter what i do, this item fails the PAT. It is coated metal so i tried to find a bare metal section and also tried the screws holding it together.
    It is possibly faulty but seems a bit strange.
    Any tips?

    Jenny

    #7276
    Charlie
    Keymaster

    Is it failing on the earth continuity test or the insulation resistance test?

    If it is failing earth continuity, there is a chance that the external metal casing of the extractor is not directly bonded to earth, or is isolated from the earthed parts internally.

    Do you have the model number? It would be worth checking the manufacturer’s instructions to confirm whether it is a Class I or Class II appliance. Even if the outside is metal, the motor and internal components may be double insulated.

    Failing that, if you can take the ducting cover part of it off easily you may be able to see where the earth bond is/should be.

    #7277
    Jenny
    Participant

    Will revist the property next week and try this advice/ get model number (I am pretty sure i checked the class – but the test was a couple of weeks ago and done other stuff since then!)
    Cheers

Viewing 3 posts - 1 through 3 (of 3 total)
  • You must be logged in to reply to this topic.